Hager MCCB h250 4P 70kA 40A LSI HEC041H – CEW Group
${shop.name} SELECT BRANCH
Cart ${totalCartItems}
Total: £${totalCart}
Shipping: £0.00
FOUND IT CHEAPER? Let us know and we'll do our best to match it! GET IN TOUCH
sale! All Hager products 5% off

Prices are VAT inclusive

Hager MCCB h250 4P 70kA 40A LSI HEC041H

Hager MCCB h250 4P 70kA 40A LSI HEC041H

Hager

HEC041H
£1,295.23 incl. VAT

- +

Moulded Case Circuit Breaker h250 4P 70kA 40A LSI
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2 100 kA
Correction factor of rating current for 6 devices placed side-by-side 1
Number of mechanical operations 4000
Electric endurance in number of cycles 1000
Altitude 2000 m
Number of poles 4 P
CE marking on label AI2_B5_CE_01.JPG
Correction factor of rating current for 4 and 5 devices placed side-by-side 1
Frequency 50;60 Hz
Range of the magnetic adjustment 224 / 280 / 350 / 448 / 504 / 532 / 560 A
Tightening torque 12Nm
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2 70 kA
Breaking capacity on 1 pole with 400 V NF 60947-2 9 kA
Protection index IP IP4X
Rated current 40 A
Thermal protection nob setting xIN 0.4 / 0.5 / 0.63 / 0.8 / 0.9 / 0.95 / 1
DIN rail mounting with optional adaptator No
Trip Unit LSI
Correction factor of rating current for 3 devices placed side-by-side 1
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2 70 kA
Connection Front connection
Correction factor of rating current for 2 devices placed side-by-side 1
Category of use A
Power loss per pole at In 0.6 W
Compatible with DIN rail mounting No
Rated insulation voltage 800 V
Rated operational voltage Ue 220 / 690 V
European directive WEEE concerned
Integrated earth fault protection No
Complete device with protection unit Yes
With under voltage release No
Pol type for printing of stamps 4P0%
Air humidity protection for all climates
Storage temperature -35/70 °C
Operating temperature -25/70 °C
Type of pole 4P4D N:0;50;100%
Connection cross-sect. flexible conductor 35 ; 150mm²
Rated impulse withstand voltage 8000 V
Type of order Toggle
Connection cross-sect. rigid cable 35 ; 185mm²
Type of connection Terminal
Number of auxiliary contacts as normally open contact 0
Number of auxiliary contacts as normally closed contact 0
Tripmode LSI
Time of response when opening 10 ms
Total power loss under IN 1.9 W
Standard text IEC 60947-2
Number of auxiliary contacts as change-over contact 0
Motor drive optional Yes
Search words Compact circuit-breaker;Circuit-breaker;Main switch;Switch;Circuit-breaker;MCCB;
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2 85 kA
Number of modules 8
EAN 3250613340643
Unit PCE
Sales status 3C
Documentations
Instruction manuals for HEC041H 1381 kb pdf Download
Commercial Distribution Catalogue 13011 kb pdf Download

We Also Recommend


Contact

Address: 362 Upper Richmond Road West, SW14 7JT, London

E-mail: shop@cewgroup.co.uk

Phone: 0800 133 7425



Payment icons
  • American Express
  • Apple Pay
  • Google Pay
  • Maestro
  • Mastercard
  • Shop Pay
  • Visa