Input PV (Only for Hybrid)
- Max. Input Power [W] 5500
- Max. Input Voltage [V] 600
- Start-up Input Voltage [V] 75
- Rated Input Voltage [V] 360
- MPPT Operating Voltage Range [V] 80 ~ 550
- Max. Input Current [A] 16 / 16
- Max. Short-circuit Current [A] 20 / 20
- No. of Independent MPP Trackers 2
- No. of Strings per MPP Tracker 1
Battery Connection
- Battery Type Lithium Battery (LFP)
- Battery Voltage [V] 80 ~ 480
- Max. Charge/Discharge Current [A] 40
- Communication Interface CAN(communicate with inverter, upgrade BMS)
AC Input and Output (Grid)
- Max. AC Input Power [VA] 7680
- Max. AC Input Current (per phase) [A] 34.9
- Rated Output Power [W] 3680
- Max. Output Apparent Power [VA] 4048/36801
- Rated Output Current (per phase) [A] 16.7/161
- Rated Output Current (per phase) [A](For AUS) 16.0
- Max. Output Current [A] 18.4
- Rated Grid Voltage [V] 220/230/240
- Rated Grid Frequency [Hz] 50/60
- Power Factor 1 ( Adjustable from 0.8 leading to 0.8 lagging )
- THDi [%] <3 @ rated power
EPS Output (With Battery)
- Max. Output Apparent Power [VA] 3680
- Peak Output Apparent Power (60s) [VA] 4400
- Max. Current (per phase) [A] 16.7
- Rated Output Voltage [V] 220/230/240
- Rated Output Frequency [Hz] 50/60
- Power Factor 1 ( Adjustable from 0.8 leading to 0.8 lagging )
- THDv ( linear Load) [%] <2 @rated power
- Parallel operation [PCS] 10
- Switch time [ms] <20
Efficiency
- Euro Efficiency [%] 95.70
- Max. Efficiency [%] 97.08
- Max. Battery Charge Efficiency (PV to BAT) (@full load) [%] 98.50
- Max. Battery Discharge Efficiency (BAT to AC) (@full load) [%] 97.00
Protection
- Insulation Monitoring YES
- Residual Current Monitoring YES
- DC Reverse Polarity Protection YES
- Anti-islanding Protection YES
- AC Short-circuit Protection YES
- AC Overcurrent/Overvoltage Protection YES
- DC Switch YES
- Battery Wack-up Function YES
- SPD DC: Type II, /AC: Type III
- AFCI Optional
General Data
- Dimensions (W*H*D) [mm] 434*418*185
- Weight [kg] 22
- Installation Wall Mounted
- Topology Non-Isolated
- Cooling Method Natural
- Noise Emission [dB] 35
- Max. Operating Altitude [m] 2000
- Operating Temperature Range [°C ] -25 ~ 60
- Humidity (No Condensation) [%] 0 ~ 100
- Ingress protection IP65
- Standby consumption[W] <15
- Monitoring Module WiFi, LAN(Optional) , 4G(Optional)
- Communication RS485, DRM, Ripple Control, USB, CAN
- Display LCD, App, Website
Standard Compliance
- Safety EN 62109-1, EN 62109-2
- Grid Regulation AS / NZS 4777.2