We support Cold Beer Friday F.C.! Get 5% off everything (except cables) – use code CBFFC5 at checkout!

Selected shop:

Selected shop:

Hager CDA263U RCCB DP A 63A 30mA

SKU: CDA263U

RCCB 2P 63A 30mA A Class

£36.97 EX. VAT

Description

Technical characteristics:

Architecture
  • Neutral position
    right
  • Number of poles
    2 P
  • Fixing mode
    DIN rail type O (symmetrical)
Main electrical features
  • Rated operational voltage Ue
    230 V
  • Frequency
    50
Voltage
  • Rated insulation voltage
    500 V
  • Rated impulse withstand voltage
    4000 V
Electric current
  • Rated residual operating current
    30 mA
  • Rated conditional short-circuit current Inc according to EN 61008-1
    6 kA
Electric current / temperature
  • Rating current 30°C
    63 A
Dimensions
  • Depth of installed product
    70 mm
  • Height of installed product
    83 mm
  • Width of installed product
    35 mm
Power
  • Total power loss under IN
    8.1 W
Tripping
  • Short-time delayed tripping
    No
Endurance
  • Electric endurance in number of cycles
    2000
  • Number of mechanical operations
    4000
Installation, mounting
  • Tightening torque
    2,8Nm
Connection
  • Connection cross-sect. flexible conductor
    16mm²
  • Connection cross-sect. rigid cable
    25mm²
  • Type of connection
    with screw
Standards
  • Standard text
    BS 61008-1,EN 61008-1
  • European directive WEEE
    concerned
Safety
  • Protection index IP
    IP20
  • Residual current type
    A
Use conditions
  • Operating temperature
    -25…40 °C

Additional information

Product

Circuit Breaker

Product Type

RCCB

Pole Configuration

Double Pole (2P)

Trip Type

Type A

Sensitivity

30 mA

Cable Capacity

16Sq.mm (Flexible) 25Sq.mm (Rigid) mm2

Width

35 mm

Current Rating

63 A

Voltage

127 | 230 V

Standards

BS EN 61008 IEC1008

Warranty

2 Years

Brand

Frequently asked questions

An RCD is a safety device designed to quickly disconnect electrical circuits when it detects an imbalance in the flow of electric current caused by a fault (such as leakage to earth). This helps prevent electric shocks and reduce the risk of electrical fires.

RCDs are commonly used in consumer units (fuse boxes) and electrical outlets in the UK. They are installed to protect circuits supplying sockets, outdoor power points, bathroom circuits, and other areas where there is a higher risk of electrical shock.

RCDs provide additional protection beyond that offered by circuit breakers (MCBs). They can detect small leakage currents (typically 30mA or less) that MCBs may not respond to, thereby offering enhanced safety against electric shock.

Yes, RCD protection is mandatory in certain circuits and situations according to UK electrical regulations (BS 7671). For example:

  • Circuits supplying socket outlets up to 32A in domestic premises.
  • Circuits supplying socket outlets up to 20A in non-domestic premises.
  • Circuits supplying mobile equipment for outdoor use (e.g., portable tools).

If an RCD trips frequently, it could indicate a fault in the circuit or a problem with connected appliances. Consulting with a qualified electrician is crucial to identify and rectify the underlying issue to maintain electrical safety.

related products