Description
Technical characteristics:
Architecture
-
Neutral positionwithout neutral
-
Number of poles1 P
-
Type of pole1 P
-
CurveC
Main electrical features
-
Rated operational voltage Ue230 / 400 V
-
Type of supply voltageAC
Voltage
-
Rated insulation voltage500 V
-
Rated impulse withstand voltage6000 V
Electric current
-
Rated service breaking capacity Ics AC according IEC 60898-17.5 kA
-
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-110 kA
Electric current / temperature
-
Rating current 30°C40 A
Dimensions
-
Depth of installed product70 mm
-
Height of installed product83 mm
-
Width of installed product17.5 mm
Power
-
Total power loss under IN3.71 W
Endurance
-
Electric endurance in number of cycles4000
-
Number of mechanical operations20000
Installation, mounting
-
Tightening torque2,8Nm
Equipment
-
Can be accessorizedYes
Standards
-
Standard textEN 60898-1,IEC 60947-2
-
European directive WEEEconcerned
Safety
-
Protection index IPIP20
Use conditions
-
Operating temperature-25…70 °C